Demonstrates IEC 62351-7 applied to real SCADA gear: devices expose health indicators and support smart polling so monitoring is built in. A lab hydrodam with SNMP shows immediate detection of a physically unplugged sensor, CPU/memory spikes after a malicious ladder logic upload, and instant alerts when backup power or redundant slots are removed. HMI process listings create a white‑list that flags unexpected tasks without installing agents. Detection is implemented with Nozomi Guardian using SNMP.