Sub-Region Failure: How to Handle the Partial Loss of a Data Center
summary
Facebook claims a single failed switchboard should never force a full-region drain and proves it by choosing the switchboard fault domain, encoding per-service constraints into an auditor (Python checks plus a dashboard), and adding a power loss siren that uses rack batteries to give ~90s to fail over. A few-thousand-server outage (≈2% of a region) once cascaded because thousands of MySQL primaries triggered Zookeeper overload; after testing by flipping breakers, most switchboards no longer require region-wide drains.