~/talk

One Measurement Layer, Many Virtual Substation Functions: RTE and EcoPhi’s 400/22...

links:none on file
slides:none on file

A 400/225 kV substation uses QMU 800 modules as a single measurement layer sampling at 2 MHz and publishing per IEC 61869 to a CMPC 800 edge running CPASS/SEAPATH; PQ, PMU/synchrophasor, PD, DFR and DFL run as virtual apps. The pilot installs ten QMU 800 units and virtualized apps instead of roughly 45 separate meters/recorders, cutting hardware by about 35 devices; systems stream real‑time signals, are in commissioning for PD thresholds, and aim to predict faults weeks ahead.

AI-written summary · about

  1. 0:00Introduction and project overview
  2. 2:53Hardware consolidation concept
  3. 7:58RTE collaboration and substation case
  4. 15:53Commissioning and next steps