The Flow of Power (Part II: Power Flow Solutions and Optimization)
summary
Per-phase analysis assumes balanced three‑phase lines so inductance and capacitance decouple and each line reduces to a pi-model with Z and Y per meter; transformers map phase voltages (delta/wye gives a √3 and 30° shift) and networks assemble into an admittance matrix so Y bus relates I and V linearly. Power flow is quadratic in voltages; DC power flow linearizes it. OPF is a nonconvex QCQP; common relaxations lift to W=vvH and drop rank-1 (SDP relaxation recovers global optima when W is rank‑1), and radial grids admit efficient exact SOCPs (tree networks admit SOCP exactness). Real‑time control uses gradient steps plus measurements, with tracking error set by problem variation, conditioning and approximation.