SCADA HMI and Microsoft Bob
summary
Demos show previously unpublished authentication flaws in SCADA HMI software (iFIX, KingView, ICONICS Genesis32) with reproducible exploits on a local VM: passwords stored XORed against a exclusive-or static key (same key per install), project files sent in cleartext across SMB, and a Genesis32 “challenge” that is a 15‑bit counter (0–~32,000) checked by taking the MD4 first‑8 response of the password so an attacker or support script can gain default admin. Tools: debugger, Process Explorer, simple XOR/byte‑flip decoders and a support‑response script; vendors are contacted.
AI-written summary · about
chapters (11)
- 0:00Introduction and panel
- 1:00Panelist introductions
- 2:06Talk overview and goals
- 7:27HMI fundamentals
- 12:48HMI security architectures
- 17:19Microsoft Bob case study
- 22:55Insecure password storage
- 27:04Crypto and XOR vulnerabilities
- 30:27InfoLink and KingView analysis
- 33:52Iconics Genesis demonstration
- 38:29Conclusion and Q&A